IPMI (Intelligent Platform Management Interface) and SNMP (Simple Network Management Protocol) Observability Setup

Configuring hardware and network monitoring for bare-metal servers and switches.

This guide explains what IPMI and SNMP monitoring collect, what credentials are required, and how to configure the inventory variables.

What Is Being Monitored​

IPMI (Bare-Metal Server Hardware)​

The IPMI exporter polls the Baseboard Management Controller (BMC) on each physical server over the network using the IPMI protocol. It collects:

  • Chassis power state — whether the server is powered on or off
  • Fan speed — RPM and health state per fan
  • Temperature — readings and health state per temperature sensor (CPU, ambient, DIMM, etc.)
  • Voltage — readings and health state per voltage rail
  • Power consumption — real-time power draw in watts (requires DCMI (Data Center Manageability Interface) support)
  • BMC info — manufacturer, model, firmware version

SNMP (Network Devices)​

The SNMP exporter polls switches and other network devices via SNMPv3. It collects:

  • Interface traffic — bytes in/out per interface
  • Interface state — link up/down, errors, drops
  • System info — hostname, description, uptime
  • IP routing stats — (optional, via ip_mib)
  • Vendor-specific hardware — (optional, e.g., dell module for Dell switches)

IPMI Setup​

What You Need Per Server​

For each bare-metal server you want to monitor, you need:

ItemDescription
BMC hostname or IPThe out-of-band management address (e.g., control0-ipmi.bcn)
IPMI usernameA dedicated monitoring account on the BMC
IPMI passwordPassword for that account

The minimum required privilege level is USER (read-only). Operator-level or Administrator-level access is not needed for metrics collection.

Credentials​

The IPMI exporter uses the same credentials for all targets that reference a given module. You can define dedicated IPMI variables or reuse the SNMP ones — they are independent.

You must create an account on each BMC with:

  • Username: a dedicated monitoring username (e.g., metrics)
  • Password: a strong password
  • Privilege: USER (read-only; sufficient for all metrics)

Inventory Configuration​

ipmi_username: metrics
ipmi_password: !vault |
$ANSIBLE_VAULT;1.1;AES256
... encrypted password ...

# IPMI targets: one entry per server BMC
ipmi_targets:
- name: "control0-ipmi" # Unique label used in Grafana
host: "control0-ipmi.bcn" # BMC hostname or IP address
module: "default" # References ipmi_exporter_modules[].name
scrape_interval: "1m" # How often to poll this target

# Module definition: maps to an ipmi_exporter configuration block
ipmi_exporter_modules:
- name: default
user: "{{ ipmi_username }}"
password: "{{ ipmi_password | trim }}"
privilege: "USER"
driver: "LAN_2_0"
collectors:
- bmc
- chassis
- dcmi
- ipmi
note

Credentials are shared across all targets that reference the same module. If servers require different credentials, define additional entries in ipmi_exporter_modules with different names and reference them via ipmi_targets[*].module.

Driver: Always Use LAN_2_0​

The driver: "LAN_2_0" setting selects IPMI 2.0 (RMCP+, Remote Management Control Protocol), which uses modern cipher suites for authentication and encryption at the protocol level. This is the correct choice for any server manufactured in the last 15+ years. IPMI 1.5 (LAN) is obsolete and should not be used.

The privilege field in ipmi_exporter_modules is the IPMI privilege level (USER, OPERATOR, ADMIN). For metrics collection, USER is sufficient.

Available Collectors​

CollectorWhat It Collects
bmcBMC manufacturer, model, firmware version
chassisChassis power state (on/off)
dcmiPower consumption in watts (requires DCMI support on BMC)
ipmiAll IPMI sensors: temperature, fans, voltage, intrusion
selSystem Event Log entries (not in default config; adds noise)

The default set (bmc, chassis, dcmi, ipmi) covers all metrics shown in the IPMI Exporter dashboard. Add sel only if you need event log monitoring.

Scrape Interval​

1m is the recommended interval for IPMI targets. Hardware sensor values change slowly, and IPMI polling generates BMC load — polling more frequently than once per minute is unnecessary and can cause issues on some BMC implementations.


SNMP Setup​

What You Need Per Device​

For each switch or network device:

ItemDescription
Device hostname or IPMust be reachable from the metrics scraper VM
SNMPv3 usernameA monitoring account configured on the device
SNMPv3 passwordAuth (and optionally priv) password
Auth/priv protocolsMatch what the device supports (see auth options below)

Defining Auth Profiles (snmp_auths)​

Auth profiles are defined in inventory under snmp_auths and referenced by name from snmp_targets[*].auth. Each profile specifies the SNMPv3 parameters for one category of device.

Fields per profile:

FieldRequiredDescription
nameyesIdentifier referenced in snmp_targets[*].auth
versionnoSNMP version, defaults to 3
usernameyesSNMPv3 username configured on the device
security_levelyesauthNoPriv (auth only) or authPriv (auth + encryption)
auth_protocolyesMD5, SHA, SHA256, SHA512
passwordyesAuth password
priv_protocolif authPrivEncryption protocol, e.g. AES
priv_passwordif authPrivEncryption password

Choosing protocols:

  • Prefer SHA or higher over MD5 if the device supports it
  • Use authPriv + AES if the management network is untrusted; authNoPriv is sufficient on isolated OOB networks

The auth field is an SNMP v3 concept and is unrelated to the IPMI privilege or driver settings.

Choosing snmp_targets[*].modules​

Modules define which SNMP MIBs to query. Each module in a target is scraped on its own interval:

ModuleMIBWhat It Collects
systemSNMPv2-MIBHostname, description, uptime
if_mibIF-MIBInterface traffic, errors, state
ip_mibIP-MIBIP routing statistics
dellDell vendor MIBDell-specific hardware status

Start with system and if_mib — these cover the SNMP dashboard. Add ip_mib if you need routing stats. Add dell only for Dell network hardware.

Scrape Interval per Module​

Set the interval based on how fast the data changes and how much resolution you need:

ModuleRecommended IntervalReason
system5mUptime and hostname change rarely
if_mib30sInterface traffic is time-sensitive
ip_mib30sRouting stats benefit from higher resolution
dell5mHardware status changes slowly

Inventory Configuration​

snmp_monitoring_password: !vault |
$ANSIBLE_VAULT;1.1;AES256
... encrypted password ...

# Define the auth profiles your devices need
snmp_auths:
- name: switch_auth # Name referenced in snmp_targets[*].auth
version: 3
username: "metrics"
security_level: authNoPriv
auth_protocol: SHA
password: "{{ snmp_monitoring_password }}"

snmp_targets:
- name: "spine-switch" # Unique label used in Grafana
host: "spine-switch.bcn" # Hostname or IP reachable from metrics scraper
auth: "switch_auth" # References snmp_auths[*].name
modules:
- name: "system"
scrape_interval: "5m"
- name: "if_mib"
scrape_interval: "30s"

Encrypting Credentials​

All passwords in the inventory must be encrypted with Ansible Vault before committing:

ansible-vault encrypt_string 'your-password-here' \
--name 'snmp_password' \
--ask-vault-password

Copy the output block (starting with !vault |) into inventory.yml. See DEPLOYMENT.md for vault setup instructions.