IPMI (Intelligent Platform Management Interface) and SNMP (Simple Network Management Protocol) Observability Setup

Configuring hardware and network monitoring for bare-metal servers and switches.

This guide explains what IPMI and SNMP monitoring collect, what credentials are required, and how to configure the inventory variables.

What Is Being Monitored

IPMI (Bare-Metal Server Hardware)

The IPMI exporter polls the Baseboard Management Controller (BMC) on each physical server over the network using the IPMI protocol. It collects:

  • Chassis power state — whether the server is powered on or off
  • Fan speed — RPM and health state per fan
  • Temperature — readings and health state per temperature sensor (CPU, ambient, DIMM, etc.)
  • Voltage — readings and health state per voltage rail
  • Power consumption — real-time power draw in watts (requires DCMI (Data Center Manageability Interface) support)
  • BMC info — manufacturer, model, firmware version

SNMP (Network Devices)

The SNMP exporter polls switches and other network devices via SNMPv3. It collects:

  • Interface traffic — bytes in/out per interface
  • Interface state — link up/down, errors, drops
  • System info — hostname, description, uptime
  • IP routing stats — (optional, via ip_mib)
  • Vendor-specific hardware — (optional, e.g., dell module for Dell switches)

IPMI Setup

What You Need Per Server

For each bare-metal server you want to monitor, you need:

ItemDescription
BMC hostname or IPThe out-of-band management address (e.g., control0-ipmi.bcn)
IPMI usernameA dedicated monitoring account on the BMC
IPMI passwordPassword for that account

The minimum required privilege level is USER (read-only). Operator-level or Administrator-level access is not needed for metrics collection.

Credentials

The IPMI exporter uses the same credentials for all targets that reference a given module. You can define dedicated IPMI variables or reuse the SNMP ones — they are independent.

You must create an account on each BMC with:

  • Username: a dedicated monitoring username (e.g., metrics)
  • Password: a strong password
  • Privilege: USER (read-only; sufficient for all metrics)

Inventory Configuration

ipmi_username: metrics
ipmi_password: !vault |
$ANSIBLE_VAULT;1.1;AES256
... encrypted password ...

# IPMI targets: one entry per server BMC
ipmi_targets:
- name: "control0-ipmi" # Unique label used in Grafana
host: "control0-ipmi.bcn" # BMC hostname or IP address
module: "default" # References ipmi_exporter_modules[].name
scrape_interval: "1m" # How often to poll this target

# Module definition: maps to an ipmi_exporter configuration block
ipmi_exporter_modules:
- name: default
user: "{{ ipmi_username }}"
password: "{{ ipmi_password | trim }}"
privilege: "USER"
driver: "LAN_2_0"
collectors:
- bmc
- chassis
- dcmi
- ipmi

Note: Credentials are shared across all targets that reference the same module. If servers require different credentials, define additional entries in ipmi_exporter_modules with different names and reference them via ipmi_targets[*].module.

Driver: Always Use LAN_2_0

The driver: "LAN_2_0" setting selects IPMI 2.0 (RMCP+, Remote Management Control Protocol), which uses modern cipher suites for authentication and encryption at the protocol level. This is the correct choice for any server manufactured in the last 15+ years. IPMI 1.5 (LAN) is obsolete and should not be used.

The privilege field in ipmi_exporter_modules is the IPMI privilege level (USER, OPERATOR, ADMIN). For metrics collection, USER is sufficient.

Available Collectors

CollectorWhat It Collects
bmcBMC manufacturer, model, firmware version
chassisChassis power state (on/off)
dcmiPower consumption in watts (requires DCMI support on BMC)
ipmiAll IPMI sensors: temperature, fans, voltage, intrusion
selSystem Event Log entries (not in default config; adds noise)

The default set (bmc, chassis, dcmi, ipmi) covers all metrics shown in the IPMI Exporter dashboard. Add sel only if you need event log monitoring.

Scrape Interval

1m is the recommended interval for IPMI targets. Hardware sensor values change slowly, and IPMI polling generates BMC load — polling more frequently than once per minute is unnecessary and can cause issues on some BMC implementations.


SNMP Setup

What You Need Per Device

For each switch or network device:

ItemDescription
Device hostname or IPMust be reachable from the metrics scraper VM
SNMPv3 usernameA monitoring account configured on the device
SNMPv3 passwordAuth (and optionally priv) password
Auth/priv protocolsMatch what the device supports (see auth options below)

Defining Auth Profiles (snmp_auths)

Auth profiles are defined in inventory under snmp_auths and referenced by name from snmp_targets[*].auth. Each profile specifies the SNMPv3 parameters for one category of device.

Fields per profile:

FieldRequiredDescription
nameyesIdentifier referenced in snmp_targets[*].auth
versionnoSNMP version, defaults to 3
usernameyesSNMPv3 username configured on the device
security_levelyesauthNoPriv (auth only) or authPriv (auth + encryption)
auth_protocolyesMD5, SHA, SHA256, SHA512
passwordyesAuth password
priv_protocolif authPrivEncryption protocol, e.g. AES
priv_passwordif authPrivEncryption password

Choosing protocols:

  • Prefer SHA or higher over MD5 if the device supports it
  • Use authPriv + AES if the management network is untrusted; authNoPriv is sufficient on isolated OOB networks

The auth field is an SNMP v3 concept and is unrelated to the IPMI privilege or driver settings.

Choosing snmp_targets[*].modules

Modules define which SNMP MIBs to query. Each module in a target is scraped on its own interval:

ModuleMIBWhat It Collects
systemSNMPv2-MIBHostname, description, uptime
if_mibIF-MIBInterface traffic, errors, state
ip_mibIP-MIBIP routing statistics
dellDell vendor MIBDell-specific hardware status

Start with system and if_mib — these cover the SNMP dashboard. Add ip_mib if you need routing stats. Add dell only for Dell network hardware.

Scrape Interval per Module

Set the interval based on how fast the data changes and how much resolution you need:

ModuleRecommended IntervalReason
system5mUptime and hostname change rarely
if_mib30sInterface traffic is time-sensitive
ip_mib30sRouting stats benefit from higher resolution
dell5mHardware status changes slowly

Inventory Configuration

snmp_monitoring_password: !vault |
$ANSIBLE_VAULT;1.1;AES256
... encrypted password ...

# Define the auth profiles your devices need
snmp_auths:
- name: switch_auth # Name referenced in snmp_targets[*].auth
version: 3
username: "metrics"
security_level: authNoPriv
auth_protocol: SHA
password: "{{ snmp_monitoring_password }}"

snmp_targets:
- name: "spine-switch" # Unique label used in Grafana
host: "spine-switch.bcn" # Hostname or IP reachable from metrics scraper
auth: "switch_auth" # References snmp_auths[*].name
modules:
- name: "system"
scrape_interval: "5m"
- name: "if_mib"
scrape_interval: "30s"

Encrypting Credentials

All passwords in the inventory must be encrypted with Ansible Vault before committing:

ansible-vault encrypt_string 'your-password-here' \
--name 'snmp_password' \
--ask-vault-password

Copy the output block (starting with !vault |) into inventory.yml. See DEPLOYMENT.md for vault setup instructions.